All the self-diagnosis and alarms identified by the GMP are stored. The user can access this information at the device's frontal panel. The shown value for each memory digit is the sum of each self-diagnosis and alarm that ever occurred to that position in hexadecimal and not only those that are active at the moment. So, it's possible to know every single alarm and self-diagnosis which has occurred since the last time the memory was cleaned (reset).
To check and clean the device's memory, follow the steps below
Self-diagnosis memory
- At any indication screen, press the keys P and ↓ simultaneously. The self-diagnosis memory screen will show up;
- Press and hold the Enter key for around 3 seconds to clean up the memory;
- If it's not possible to clean a code, it means that the code is active at the moment;
- Press the P key to go back to the indication screens.
Alarms memory
- At any indication screen, press both P and ↑ keys. The alarms screen will show up;
- Press and hold the Enter key for around 3 seconds to clean up the memory;
- If it's not possible to clean a code, it means that code is active at the moment;
- Press the P key to go back to the indication screens.
If you have any problems or difficulties with the procedure, please do not hesitate to contact us!
Contacts:
Telephone: +55 (11) 2410 – 1190 — Ext. 425
Cellular: +55 (11) 97225 – 8683 - WhatsApp
E-mail: [email protected]
Customer Service Portal
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article