Final procedures to get GMP working

Modified on Wed, 04 Oct 2023 at 03:46 PM

After installing GMP, follow the steps below to put it to work:

  1. Do all equipment parameterization;
  2. Adjust the clock (MENU →  CLCK);
  3. Clean up the self-diagnosis memory (see How to check and clean GMP self-diagnosis memory and alarms);
  4. Clean up the alarms memory (see How to check and clean GMP self-diagnosis memory and alarms);
  5. Reset the device log (MENU → ADVC → LOG → RSET).
  6. Reset the H2 measurement learning (MENU → ADVC → H2 → LERN);
  7. Wait around 10 minutes to verify the self-diagnosis memory. If it still has a self-diagnosis, check the reason for it and clean up again (see How to check and clean GMP self-diagnosis memory and alarms).

 Every time the GMP installation environment change (new installation or changing the installation local) must reset the H2 measurement leaning (item 6 above). 