After installing GMP, follow the steps below to put it to work:
- Do all equipment parameterization;
- Adjust the clock (MENU → CLCK);
- Clean up the self-diagnosis memory (see How to check and clean GMP self-diagnosis memory and alarms);
- Clean up the alarms memory (see How to check and clean GMP self-diagnosis memory and alarms);
- Reset the device log (MENU → ADVC → LOG → RSET).
- Reset the H2 measurement learning (MENU → ADVC → H2 → LERN);
- Wait around 10 minutes to verify the self-diagnosis memory. If it still has a self-diagnosis, check the reason for it and clean up again (see How to check and clean GMP self-diagnosis memory and alarms).
⚠ Every time the GMP installation environment change (new installation or changing the installation local) must reset the H2 measurement leaning (item 6 above).