Final procedures to get GMP working

Created by Patrícia Siqueira, Modified on Wed, 4 Oct, 2023 at 3:46 PM by Patrícia Siqueira

After installing GMP, follow the steps below to put it to work:

  1. Do all equipment parameterization;
  2. Adjust the clock (MENU →  CLCK);
  3. Clean up the self-diagnosis memory (see How to check and clean GMP self-diagnosis memory and alarms);
  4. Clean up the alarms memory (see How to check and clean GMP self-diagnosis memory and alarms);
  5. Reset the device log (MENU → ADVC → LOG → RSET).
  6. Reset the H2 measurement learning (MENU → ADVC → H2 → LERN);
  7. Wait around 10 minutes to verify the self-diagnosis memory. If it still has a self-diagnosis, check the reason for it and clean up again (see How to check and clean GMP self-diagnosis memory and alarms).

 Every time the GMP installation environment change (new installation or changing the installation local) must reset the H2 measurement leaning (item 6 above). 


If you have any problems or difficulties with the procedure, please do not hesitate to contact us!

Contacts:  
Telephone: +55 (11) 2410 – 1190 — Ext. 425
Cellular: +55 (11) 97225 – 8683 - WhatsApp
E-mail: sac@treetech.com.br
Customer Service Portal

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article