Alarm memory - LAP

Created by Patrícia Siqueira, Modified on Wed, 3 Jan at 2:43 PM by Patrícia Siqueira

1. Viewing the alarm memory

The Alarm Memory function allows you to know all events that occurred in the LAP, such as forced cooling activation, alarms, and shutdowns. This memory is non-volatile and cumulative, meaning it allows you to know all events that occurred, but not when they occurred. 

The Alarm Memory is accessed by simultaneously pressing the Ícone 
Descrição gerada automaticamente and Ícone 
Descrição gerada automaticamente buttons. The alarm sets ALM1 and ALM2 will be displayed on the screen and will alternate with the alarm code. It is possible to navigate between these sets using the and Ícone 
Descrição gerada automaticamente buttons.

To reset the Alarm Memory, press the Ícone 
Descrição gerada automaticamente button for 5 seconds. If there is any active alarm, the memory will be reset, already indicating its occurrence. Press the Ícone 
Descrição gerada automaticamente button to return to the indication screen.

The alarms are indicated in hexadecimal format, but as there are more error codes than would be possible to indicate with only 4 digits, it is necessary to use two sets (ALM1 and ALM2) to indicate them. In the case of two different events, the result displayed in the position relative to this event is a sum of them. Below is the table with possible error combinations for each digit.

Code

Description

0

No active alarms

1

Alarm 1 active

2

Alarm 2 active

3

Alarms 1 and 2 active

4

Alarm 4 active

5

Alarms 1 and 4 active

6

Alarms 2 and 4 active

7

Alarms 1, 2 and 4 active

8

Alarm 8 active

9

Alarms 1 and 8 active

A

Alarms 2 and 8 active

B

Alarms 1, 2 and 8 active

C

Alarms 4 and 8 active

D

Alarms 1, 4 and 8 active

E

Alarms 2, 4 and 8 active

F

Alarms 1, 2, 4, and 8 active

To understand each alarm code on the display, consult the following table:

ALM1

Code

Description

0000

No alarm

0001

High-temperature alarm on RTD1

0002

Shutdown alarm on RTD1

0004

Delay shutdown alarm on RTD1

0008

High-temperature alarm on RTD2

0010

Shutdown alarm on RTD2

0020

Delay shutdown alarm on RTD2

0040

High-temperature alarm on RTD3

0080

Shutdown alarm on RTD3

0100

Delay shutdown alarm on RTD3

0200

High-temperature alarm on RTD4

0400

Shutdown alarm on RTD4

0800

Delay shutdown alarm on RTD4

1000

High-temperature alarm on RTD5

2000

Shutdown alarm on RTD5

4000

Delay shutdown alarm on RTD5

8000

High-temperature alarm on RTD6

ALM2

Code

Description

0000

No alarm

0001

Shutdown alarm on RTD6

0002

Delay shutdown alarm on RTD6

0004

Low winding 1 lifetime alarm 

0008

Low percentage of useful life for winding 1 alarm

0010

Low winding 2 lifetime alarm

0020

Low percentage of useful life for winding 2 alarm

0040

Low winding 3 lifetime alarm

0080

Low percentage of useful life for winding 3 alarm

0100

Low winding 4 lifetime alarm

0200

Low percentage of useful life for winding 4 alarm

0400

Low winding 5 lifetime alarm

0800

Low percentage of useful life for winding 5 alarm

1000

Low winding 6 lifetime alarm

2000

Low percentage of useful life for winding 6 alarm


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article