MBR_v2 - Device Profile

Criada por Jane Chia Tsyr Chen, Modificado em Qua, 17 Jul na (o) 2:10 PM por Jane Chia Tsyr Chen

DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: Treetech Tecnologia
Device Name: MBR_v2 - Relé de Ruptura de Membrana/Bolsa
Highest DNP Level Supported:Device Function:
For Requests: Level 1( ) Master
For Responses: Level 1(X) Remote
Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:
Reads of Binary Inputs (Object 01, Variation 01, Qualifier 06)
Reads of Binary Inputs (Object 01, Variation 02, Qualifier 06, 17 and 28)
Reads of Binary Input Event (Object 02, Variation 01, 02 and 03, Qualifier 18 and 27)
Reads of Binary Outputs (Object 10, Variation 01, Qualifier 00 and 01)
Reads of Binary Outputs (Object 10, Variation 02, Qualifier 00, 01, 17 and 28)
Reads of Analog Inputs (Object 30, Variation 01, 02, 03 and 04, Qualifier 06, 17 and 28)
Reads of Analog Output Status (Object 40, Variation 01, Qualifier 00, 01, 06, 17 and 28)
Reads of Analog Output Status (Object 40, Variation 02, Qualifier 06, 17 and 28)
Writes of Analog Outputs (Object 41, Variation 01, Qualifier 17 and 28)
Reads Class Objects (Object 60, Variation 02, Qualifier 18 and 27)

GENERAL INFORMATION:
Maximum Data Link Frame Size (octets):Maximum Application Frame Size (octets):
Transmitted: 292Transmitted: 2000
Received: (must be 292)Received: 249
Maximum Data Link Re-tries:Maximum Application Layer Re-tries:
( ) None(X) None
(x) Fixed at 0( ) Configurable, range ___ to ___
( ) Configurable, range 0 to 255(Fixed is not permitted)
Requires Data Link Layer Confirmation:
(X) Never
( ) Always
( ) Sometimes If Sometimes, when? ______________________________
( ) Configurable as: _______________________________________________
Requires Application Layer Confirmation:
( ) Never
( ) Always (Not recommended)
(X) When reporting Event Data (Slave devices only)
( )  When sending mult-fragment responses (Slave devices only)
( ) Sometimes: If ‘Sometimes’, when? __________________________________________
( ) Configurable: If ‘Configurable’, how? _______________________________________
Timeouts while waiting for:
Data link confirm:                                                 ( ) None(X) Fixed at 100 ms( ) Variable*( ) Configurable*
Complete Appl. Fragment:(X) None( ) Fixed at ____( ) Variable*( ) Configurable*
Aplication Confirm:( ) None(X) Fixed at 5s( ) Variable*( ) Configurable*
Complete Appl. Response:(X) None( ) Fixed at ____( ) Variable*( ) Configurable*
Others: ______________________________________________________________________
*Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout
Sends/Executes Control Operations:
WRITE Binary Outputs:(X) Never( ) Always( ) Sometimes*( )Configurable*
SELECT/OPERATE:(X) Never( ) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE:( ) Never(X) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE-No ACK:( ) Never(X) Always( ) Sometimes*( )Configurable*





Count > 1:(X) Never( ) Always( ) Sometimes*( )Configurable*
Pulse On:(X) Never( ) Always( ) Sometimes*( )Configurable*
Pulse Off:(X) Never( ) Always( ) Sometimes*( )Configurable*
Latch On:( ) Never(X) Always( ) Sometimes*( )Configurable*
Latch Off:( ) Never(X) Always( ) Sometimes*( )Configurable*





Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
Clear Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
*Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.





FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:
Expects Binary Input Change Events:
( ) Either time-tagged or non-time-tagged for a single event.
( ) Both time-tagged and non-time-tagged for a single event.
( ) Configurable (Attach explanation)





FILL OUT THE FOLLOWING ITEM FOR REMOTE DEVICES ONLY:
Default Status Object/Variation:Default Analog Object/Variation:
( ) No Status objects reported( ) No Analog objects reported
( ) Configurable (attach explanation)( ) Configurable (attach explanation)
( ) Default Static Object__________( ) Default Static Object______________
( ) Default Static Variation __________( ) Default Static Variation ___________
( ) Default Event Object___________( ) Default Event Object______________
( ) Default Event Variation __________( ) Default Event Variation ___________
(X) Point-by-point list attached(X) Point-by-point list attached
Default Counter Object/Variation:Counters Roll Over at:
(X) No Counters reported(X) No Counters reported
( ) Configurable (attach explanation)( ) Configurable (attach explanation)
( ) Default Static Object_____________( ) 16 Bits
( ) Default Static Variation __________( ) 32 Bits
( ) Default Event Object_____________( ) Other Value _________
( ) Default Event Variation __________( ) Point-by-point list attached
( ) Point-by-point list attached
Default Frozen Counter Object/Variation:Counters frozen by means of:
(X) No Frozen Counters reported(X) No Frozen Counters reported
( ) Configurable (attach explanation)( ) Remote device time based
( ) Default Static Object_____________( ) Fixed time
( ) Default Static Variation __________( ) Configurable; range _____ to _____
( ) Default Event Object_____________( ) Master Request (see implementation table)
( ) Default Event Variation __________( ) Both
( ) Point-by-point list attached
Analog Deadbands:Configuring Analog Deadbands:
( ) Fixed(X) Not Applicable
( ) Configurable: ____( ) Configuration Software
(X) Per point( ) Using Object 34 from the master station
( ) Per Analog Type( ) Both configuration software and Object 34
( ) Global
Are the updated deadband values preserved through a device reset:
(X) YES
( ) NO
The number of multiple objects allowed in a single read request message:
Number of multiple objects allowed: 3
Ability to DISABLE/ENABLE DNP database points:IIN 1-6 Device Trouble Bit:
(X) Not Applicable( ) Never used
( ) Per point(X) Reason for setting: Device busy
( ) Per object
( ) Global
Time Sync Information:
Time Sync Period:
( ) Never
(X) Fixed at 86400 seconds
( ) Configurable, range ______ to _______ seconds
a) Maximum time base drift over a 10 minute interval:             _________ ms
b) Maximum Internal Time Reference Error when set via DNP: _________ ms
c) Maximum Delay Measurement error: _________ ms
d) Maximum Response time: _________ ms
e) Event data time-tag error – if different than ( c ) :
f) Binary Input Change Events __________ ms
g) Counter Change Events __________ ms
h) Frozen Counter Change Events __________ ms
i) Analog Change Events __________ ms
j) Frozen Analog Change Events      __________ ms
Sends/Executes Digital Control Operations:
SELECT/OPERATE**(X) Never( ) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE**( ) Never(X) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE – NO ACK**( ) Never(X) Always( ) Sometimes*( )Configurable*





Count > 1:(X) Never( ) Always( ) Sometimes*( )Configurable*
Pulse On:(X) Never( ) Always( ) Sometimes*( )Configurable*
Pulse Off:(X) Never( ) Always( ) Sometimes*( )Configurable*
Latch On:( ) Never(X) Always( ) Sometimes*( )Configurable*
Latch Off:( ) Never(X) Always( ) Sometimes*( )Configurable*
Trip/Close:(X) Never( ) Always( ) Sometimes*( )Configurable*
Raise/Lower:(X) Never( ) Always( ) Sometimes*( )Configurable*





Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
Clear Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.
**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.
Sends/Executes Analog Control Operations:
SELECT/OPERATE**(X) Never( ) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE**( ) Never(X) Always( ) Sometimes*( )Configurable*
DIRECT OPERATE – NO ACK**( ) Never(X) Always( ) Sometimes*( )Configurable*





Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
Clear Queue:(X) Never( ) Always( ) Sometimes*( )Configurable*
*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.
**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.
The maximum number of objects supported in a single control request for objects 12 and 41.
Number of objects allowed for object 12: 20
Number of objects allowed for object 41: 20
Control Points per address:Do all indices support the same control codes:
( ) Configurable(X) YES – Controls codes 3 and 4
(X) 1 control point per address( ) NO – attached points list stating configuration ability and supported control codes per point or group of points
( ) 2 control points per address
Maximum Select/Execute Delay Time:Ability for REMOTE/LOCAL control mode:
(X) Not Applicable(X) Not Applicable
( ) Fixed at _____ seconds( ) Per point
( ) Configurable, range ______ to ______ seconds( ) Per object

( ) Global
Sends Unsolicited Responses:Sends Static Data in Unsolicited Responses:
(X) Never(X) Never
( ) Configurable (attach explanation)( ) When Device Restarts
( ) Only certain objects( ) When Status Flags Change
( ) Sometimes (attach explanation)*No other options permitted.
ENABLE/DISABLE Unsolicited:Minimum number of events and/or minimum time before transmission of an unsolicited message.
(X) Not SupportedNumber of events: __________
( ) ConfigurableMinimum amount of time (msec) : ___________
( ) Function codes 20,21 supported
Assign Class Function code supported:Is the Event Buffer size configurable:
(X) NO(X) NO fixed size: _______
( ) YES( ) YES: range: __________ to __________
( ) Per ObjectConfigurable Per Class buffer:
( ) Per Point(X) NO
( ) Configurable( ) YES
Are the updated ENABLE/DISABLE unsolicited settings saved through a device reset:Are the updated Assign Class settings saved through a device reset:
( ) YES( ) YES
(X) NO(X) NO
Supports Collision Avoidance:
(X) Never
( ) Always (attach explanation)
( ) Configurable (attach explanation)
Source Address Filtering:
(X) Not Supported
( ) Configurable (attach explanation)
Supports Multi-drop communications:          (X) YES          ( ) NO
Sends Multi-Fragment Responses:              (X) YES          ( ) NO



Logo da Treetech

Este artigo foi útil?