To check if the MO probe is functioning properly, follow the tests outlined in the table below:
Sensor Test - MO Probe (Humidity) | |||
MO probe | Multimeter | Result | Range |
4 | - | -0,530 | |
5 | |||
6 | + | +0,545 |
MO probe | Multimeter | Result | Range |
4 | - | -0,670 | |
5 | + | ||
6 | +0,710 |
MO probe | Multímetro | Result | Range |
4 | + | Aberto | |
5 | |||
6 | - | Aberto |
⚠ The multimeter should be set to the diode measurement mode.
If there is any problem or you encounter difficulty with the procedure, do not hesitate to contact us!