GMP - Parameter definition table

Created by Deleted Agent, Modified on Mon, 15 Aug 2022 at 02:12 PM by Patrícia Siqueira

Serial Nº Interface module: 

Date:


MENU
Parameter
Description
Adjusted Value
Unit



ALRM
H2H
High H2 alarm
ppm
H2VH
Very high H2 alarm
ppm
H2OHHigh water content alarm
ppm
H2OVVery high water content alarm
ppm
W20HHigh water content at 20 °C alarm
ppm
W20VVery high water content at 20 °C alarm

ppm
RSHHigh relative saturation alarm 
%
RSVHVery high relative saturation alarm
%
H2THigh H2 trend alarm 
dias
H2OTHigh water trend alarm

dias
W20TWater trend at 20 °C alarm
dias
ALMHAlarm hysteresis value
%

 

 

CONF
BDR
Serial communication Baud-rate 
Kbps
PRT
Communication protocol
 
END
Address in RS-485 (to Modbus® protocol)
 
END1
Address 1st part in RS485 (to DNP3 protocol)

END2
Address 2st part in RS485 (to DNP3 protocol)

DLTX
Data trasmition delay
ms
DLRX
Data reciver delay
ms


 

OIL
A1
Constant A of water solubility, uniti and decimal

A2
Constant A of water solubility, hundredths

B
Constant B of water solubility

TREF
Reference Temperature
°C
RSCL
Relative saturation calibration
%
RSEP
Relative saturation limit aplication value
%
RSNP
Relative saturation nominal point equals to the calibration
%
TTCW
Water trend time constant
h
FH2O
Filter rate of relative water and oil temperature


 
H2
H2CL
H2 calibration
ppm
TTCH
H2 trend time constant

FLH2
Filter rate of relative H2 

LERN
Starts the H2 learning 



ADVC

CONF
DISPDisplay mode 




NPWDNew password 




LOG
TIMELOG Recording time interval




min
VARIVariation in the measurements for recording purposes 



%
RSTLOG Reset 





RL1
RL2
RL3
RL4

RLAY
RL
MODE

Logic of the relay Normal/Inverted (NC/NO)






H2Define H2 alarms that activate the relay




H2ODefine H2O alarms that activate the relay





TRNDIt associates the relay to trend alarms





DIAGIt associates the relay to self-diagnostic alarms





RDET
H2HTriggers the relay by high H2 alarm





H2VHTriggers the relay by very high H2 alarm





H2OHTriggers  the relay by high H2O alarm





H2OVTriggers the relay by very high H2O alarm





W2OHTriggers the relay by high H2O at 20 °C alarm




W20VTriggers the relay by very high H2O at 20 °C alarm





RSHTriggers the relay by high relative saturation




RSVHTriggers the relay by very high relative saturation





H2THTriggers the relay by amount of days until reach a high H2 level




H2TVTriggers the relay by amount of days until reach a very high H2 level





WTHTriggers the relay by amount of days until reach a high H2O level




WTVTriggers the relay by amount of days until reach a very high H2O level





20THTriggers the relay by amount of days until reach a high H2O level at 20 °C





20TVTriggers the relay by amount of days until reach a very high H2O level at 20 °C





ANOU
AORRange of analog outputs
mA
AV1Variable of analog output 1 

BOS1Beginning of the scale of analog output 1

EOS1End of the scale of analog output 1


AV2Variable of analog output 2


BOS2Beginning of the scale of analog output 2


EOS2End of the scale of analog output 2


ANOT
ANO1
Tests the analog output 1

ANO2
Tests the analog output 2