BM - DNP3 Device Profile

Criada por Stephanye Martins, Modificado em Ter, 22 Out na (o) 11:52 AM por Gabriel Cuba dos Santos Cuba dos Santos Neto

DNP V3.0
DEVICE PROFILE
Vendor Name: Treetech Sistemas Digitais
Device Name: BM - Monitor de Buchas On-Line (BM-HMI)

Highest DNP Level Supported:

For Requests: Level 1

For Responses: ______

Device Function:

( ) Master

(X) Remote

Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:

  • Reads of Binary Inputs (Object 01, Variation 02, Qualifier 00, 01 and 06)

  • Reads of 16-bit Analog Inputs (Object 30, Variation 02, Qualifier 00, 01 and 06)

GENERAL INFORMATION:

Maximum Data Link Frame Size (octets):

Transmitted: 292

Received: (must be 292)

Maximum Application Frame Size (octets):

Transmitted: 700

Received: 50

Maximum Data Link Re-tries:

(X) None

( ) Fixed at ___

( ) Configurable, range 0 to 255

Maximum Application Layer Re-tries:

(X) None

( ) Configurable, range ___ to ___

(Fixed is not permitted)

Requires Data Link Layer Confirmation:

(X) Never

( ) Always

( ) Sometimes If Sometimes, when? ______________________________

( ) Configurable as: _______________________________________________

Requires Application Layer Confirmation:

( ) Never

( ) Always (Not recommended)

(X) When reporting Event Data (Slave devices only)

( ) When sending mult-fragment responses (Slave devices only)

( ) Sometimes: If ‘Sometimes’, when? __________________________________________

( ) Configurable: If ‘Configurable’, how? _______________________________________

Timeouts while waiting for:

Data link confirm: Complete Appl. Fragment:

Aplication Confirm:

Complete Appl. Response:

(X) None

(X) None

(X) None

(X) None
( ) Fixed at ____

( ) Fixed at ____


( ) Fixed at ____


( ) Fixed at ____
( ) Variable*

( ) Variable*

( ) Variable*

( ) Variable*
( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

Others: ______________________________________________________________________

*Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout

Sends/Executes Control Operations:

WRITE Binary Outputs:

SELECT/OPERATE:

DIRECT OPERATE:

DIRECT OPERATE-No ACK:

 

Count > 1:

Pulse On:

Pulse Off:

Latch On:

Latch Off:


Queue:

Clear Queue:

(X) Never 
(X) Never 
( ) Never
( ) Never

(X) Never 
(X) Never 
(X) Never 
( ) Never
( ) Never

(X) Never 
(X) Never
( ) Always
( ) Always
(X) Always
(X) Always

( ) Always
( ) Always
( ) Always
(X) Always
(X) Always

( ) Always
( ) Always
( ) Sometimes*
( ) Sometimes*
( ) Sometimes*
( ) Sometimes*

( ) Sometimes*
( ) Sometimes*
( ) Sometimes*
( ) Sometimes*
( ) Sometimes*

( ) Sometimes*
( ) Sometimes*

( ) Configurable*
( ) Configurable*
( ) Configurable*
( ) Configurable*

( ) Configurable*
( ) Configurable* 
( ) Configurable* 
( ) Configurable* 
( ) Configurable* 

( ) Configurable* 
( ) Configurable* 
*Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.



FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:

Expects Binary Input Change Events:

( ) Either time-tagged or non-time-tagged for a single event.

( ) Both time-tagged and non-time-tagged for a single event.

( ) Configurable (Attach explanation)



FILL OUT THE FOLLOWING ITEM FOR REMOTE DEVICES ONLY:

Default Status Object/Variation:

( ) No Status objects reported

( ) Configurable (attach explanation)

( ) Default Static Object_____________

( ) Default Static Variation __________

( ) Default Event Object_____________

( ) Default Event Variation __________

(X) Point-by-point list attached

Default Analog Object/Variation:

( ) No Analog objects reported

( ) Configurable (attach explanation)

( ) Default Static Object______________

( ) Default Static Variation ___________

( ) Default Event Object______________

( ) Default Event Variation ___________

(X) Point-by-point list attached

Default Counter Object/Variation:

(X) No Counters reported

( ) Configurable (attach explanation)

( ) Default Static Object_____________

( ) Default Static Variation __________

( ) Default Event Object_____________

( ) Default Event Variation __________

( ) Point-by-point list attached

Counters Roll Over at:

(X) No Counters reported

( ) Configurable (attach explanation)

( ) 16 Bits

( ) 32 Bits

( ) Other Value _________

( ) Point-by-point list attached


Default Frozen Counter Object/Variation:

(X) No Frozen Counters reported

( ) Configurable (attach explanation)

( ) Default Static Object_____________

( ) Default Static Variation __________

( ) Default Event Object_____________

( ) Default Event Variation __________

( ) Point-by-point list attached

Counters frozen by means of:

(X) No Frozen Counters reported

( ) Remote device time based

( ) Fixed time

( ) Configurable; range _____ to _____

( ) Master Request (see implementation table)

( ) Both


Analog Deadbands:

( ) Fixed

( ) Configurable: ____

(X) Per point

( ) Per Analog Type

( ) Global

Configuring Analog Deadbands:

(X) Not Applicable

( ) Configuration Software

( ) Using Object 34 from the master station

( ) Both configuration software and Object 34


Are the updated deadband values preserved through a device reset:

(X) YES

( ) NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: 1

Ability to DISABLE/ENABLE DNP database points:

(X) Not Applicable

( ) Per point

( ) Per object

( ) Global

IIN 1-6 Device Trouble Bit:

(X) Never used

( ) Reason for setting:

Time Sync Information:

Time Sync Period:

(X) Never

( ) Fixed at ______ seconds

( ) Configurable, range ______ to _______ seconds

a) Maximum time base drift over a 10 minute interval:             _________ ms
b) Maximum Internal Time Reference Error when set via DNP: _________ ms
c) Maximum Delay Measurement error: _________ ms
d) Maximum Response time: _________ ms
e) Event data time-tag error – if different than ( c ) :
f) Binary Input Change Events __________ ms
g) Counter Change Events __________ ms
h) Frozen Counter Change Events __________ ms
i) Analog Change Events __________ ms
j) Frozen Analog Change Events      __________ ms

Sends/Executes Digital Control Operations:

SELECT/OPERATE:

DIRECT OPERATE:

DIRECT OPERATE-No ACK:

 

Count > 1:

Pulse On:

Pulse Off:

Latch On:

Latch Off:

Trip/Close:

Raise/Lower:

 

Queue:

Clear Queue:


(X) Never 
( ) Never
( ) Never

(X) Never  
(X) Never 
(X) Never 
( ) Never
( ) Never

(X) Never 
(X) 
Never 


(X) Never
(X) 
Never
( ) Always  
(X) Always 
(X) Always 


( ) Always

( ) Always   
( ) Always 
(X) Always 
(X) Always 

( ) Always 
( ) Always 


( ) Always 
( ) 
Always
( ) Sometimes* 
( ) Sometimes* 
( ) Sometimes* 

( ) Sometimes*

( ) Sometimes* 
( ) Sometimes* 
( ) Sometimes* 
( ) Sometimes* 

( ) Sometimes*
( ) Sometimes*
 

( ) Sometimes* 
( ) 
Sometimes*
( ) Configurable* 
( ) Configurable*  
( ) Configurable*  

( ) Configurable*  
( ) Configurable*  
( ) Configurable*  
( ) Configurable*  
( ) Configurable*  

( ) Configurable*  
( ) Configurable* 
 


( ) Configurable*  
( ) 
Configurable* 

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.

Sends/Executes Analog Control Operations:

SELECT/OPERATE**

DIRECT OPERATE**

DIRECT OPERATE-No ACK**


Queue:

Clear Queue:


(X) Never 
( ) Never
( ) Never



(X) Never 
(X) Never 

( ) Always 
(X) Always 
(X) Always 



( ) Always  
( ) Always

( ) Sometimes*
( ) Sometimes*
( ) Sometimes*



( ) Sometimes*
( ) Sometimes*

( ) Configurable*
( ) Configurable*
( ) Configurable*



( ) Configurable*
( ) Configurable*

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.

The maximum number of objects supported in a single control request for objects 12 and 41.

Number of objects allowed for object 12: 1

Number of objects allowed for object 41: 1

Control Points per address:

( ) Configurable

(X) 1 control point per address

( ) 2 control points per address

Do all indices support the same control codes:

(X) YES – Controls codes 3 and 4

( ) NO – attached points list stating configuration ability and supported control codes per point or group of points

Maximum Select/Execute Delay Time:

(X) Not Applicable

( ) Fixed at _____ seconds

( ) Configurable, range ______ to ______ seconds


Ability for REMOTE/LOCAL control mode:

(X) Not Applicable

( ) Per point

( ) Per object

( ) Global

Sends Unsolicited Responses:

(X) Never

( ) Configurable (attach explanation)

( ) Only certain objects

( ) Sometimes (attach explanation)

Sends Static Data in Unsolicited Responses:

(X) Never

( ) When Device Restarts

( ) When Status Flags Change

*No other options permitted.

ENABLE/DISABLE Unsolicited:

(X) Not Supported

( ) Configurable

( ) Function codes 20,21 supported

Minimum number of events and/or minimum time before transmission of an unsolicited message.

Number of events: __________

Minimum amount of time (msec) : ___________

Assign Class Function code supported:

(X) NO

( ) YES

( ) Per Object

( ) Per Point

( ) Configurable

Is the Event Buffer size configurable:

(X) NO fixed size: _______

( ) YES: range: __________ to __________

Configurable Per Class buffer:

(X) NO

( ) YES

Are the updated ENABLE/DISABLE unsolicited settings saved through a device reset:

( ) YES

(X) NO

Are the updated Assign Class settings saved through a device reset:

( ) YES

(X) NO

Supports Collision Avoidance:

(X) Never

( ) Always (attach explanation)

( ) Configurable (attach explanation)

Source Address Filtering:

(X) Not Supported

( ) Configurable (attach explanation)

Supports Multi-drop communications:            (X) YES                   ( ) NO
Sends Multi-Fragment Responses:                (X) YES                   ( ) NO




Este artigo foi útil?

Que bom!

Obrigado pelo seu feedback

Desculpe! Não conseguimos ajudar você

Obrigado pelo seu feedback

Deixe-nos saber como podemos melhorar este artigo!

Selecione pelo menos um dos motivos
A verificação do CAPTCHA é obrigatória.

Feedback enviado

Agradecemos seu esforço e tentaremos corrigir o artigo