SD+ - Device profile

Criada por Stephanye Martins, Modificado em Thu, 11 Jan 2024 na (o) 09:01 AM por Patrícia Siqueira

DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: Treetech Tecnologia LTDA
Device Name: SD+ - Smart device gateway

Highest DNP Level Supported:

For Requests: Level 1

For Responses: ______

Device Function:

(   ) Master

( X ) Remote

Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:

  • Reads of Binary Inputs (Object 01, Variation 01, Qualifier 00, 01 and 06)

  • Reads of 16-bit Analog Inputs (Object 30, Variation 04 Qualifier 00, 01 and 06)

GENERAL INFORMATION:

Maximum Data Link Frame Size (octets):

Transmitted: 292

Received: (must be 292)

Maximum Application Frame Size (octets):

Transmitted: 800

Received: 50

Maximum Data Link Re-tries:

( X ) None

(   ) Fixed at ___

(   ) Configurable, range 0 to 255

Maximum Application Layer Re-tries:

( X ) None

(   ) Configurable, range ___ to ___

(Fixed is not permitted)

Requires Data Link Layer Confirmation:

( X ) Never

(   ) Always

(   ) Sometimes If Sometimes, when? ______________________________

(   ) Configurable as: _______________________________________________

Requires Application Layer Confirmation:

(   ) Never

(   ) Always (Not recommended)

( X ) When reporting Event Data (Slave devices only)

(   )  When sending mult-fragment responses (Slave devices only)

(   ) Sometimes: If ‘Sometimes’, when? __________________________________________

(   ) Configurable: If ‘Configurable’, how? _______________________________________

Timeouts while waiting for:

Data link confirm:  

Complete Appl. Fragment:

Aplication Confirm:

Complete Appl. Response:

(X) None

(X) None

(X) None

(X) None

( ) Fixed at ____

( ) Fixed at ____

( ) Fixed at ____

( ) Fixed at ____

( ) Variable*

( ) Variable*

( ) Variable*

( ) Variable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

Others: ______________________________________________________________________

*Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout

Sends/Executes Control Operations: 

WRITE Binary Outputs:

SELECT/OPERATE:

DIRECT OPERATE:

DIRECT OPERATE-No ACK:

 

Count > 1:

Pulse On:

Pulse Off:

Latch On:

Latch Off:

 

Queue:

Clear Queue:


(X) Never

(X) Never

( ) Never

( ) Never

 

(X) Never

(X) Never

(X) Never

( ) Never

( ) Never

 

(X) Never

(X) Never


( ) Always

( ) Always

(X) Always

(X) Always

 

( ) Always

( ) Always

( ) Always

(X) Always

(X) Always

 

( ) Always

( ) Always


( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

 

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

 

( ) Sometimes*

( ) Sometimes*


( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

 

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

 

( ) Configurable*

( ) Configurable*


*Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation. 

FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:
Expects Binary Input Change Events:

(   ) Either time-tagged or non-time-tagged for a single event.

(   ) Both time-tagged and non-time-tagged for a single event.

(   ) Configurable (Attach explanation)


FILL OUT THE FOLLOWING ITEM FOR REMOTE DEVICES ONLY:

Default Status Object/Variation:

(   ) No Status objects reported

(   ) Configurable (attach explanation)

(   ) Default Static Object_____________

(   ) Default Static Variation __________

(   ) Default Event Object_____________

(   ) Default Event Variation __________

( X ) Point-by-point list attached

Default Analog Object/Variation:

(   ) No Analog objects reported

(   ) Configurable (attach explanation)

(   ) Default Static Object______________

(   ) Default Static Variation ___________

(   ) Default Event Object______________

(   ) Default Event Variation ___________

( X ) Point-by-point list attached

Default Counter Object/Variation:

( X ) No Counters reported

(   ) Configurable (attach explanation)

(   ) Default Static Object_____________

(   ) Default Static Variation __________

(   ) Default Event Object_____________

(   ) Default Event Variation __________

(   ) Point-by-point list attached

Counters Roll Over at:

( X ) No Counters reported

(   ) Configurable (attach explanation)

(   ) 16 Bits

(   ) 32 Bits

(   ) Other Value _________

(   ) Point-by-point list attached

Default Frozen Counter Object/Variation:

( X ) No Frozen Counters reported

(   ) Configurable (attach explanation)

(   ) Default Static Object_____________

(   ) Default Static Variation __________

(   ) Default Event Object_____________

(   ) Default Event Variation __________

(   ) Point-by-point list attached

Counters frozen by means of:

( X ) No Frozen Counters reported

(   ) Remote device time based

(   ) Fixed time

(   ) Configurable; range _____ to _____

(   ) Master Request (see implementation table)

(   ) Both

Analog Deadbands:

(   ) Fixed

(   ) Configurable: ____

( X ) Per point

(   ) Per Analog Type

(   ) Global

Configuring Analog Deadbands:

( X ) Not Applicable

(   ) Configuration Software

(   ) Using Object 34 from the master station

(   ) Both configuration software and Object 34



Are the updated deadband values preserved through a device reset:

( X ) YES

(   ) NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: 3

Ability to DISABLE/ENABLE DNP database points:

( X ) Not Applicable

(   ) Per point

(   ) Per object

(   ) Global

IIN 1-6 Device Trouble Bit:

( X ) Never used

(   ) Reason for setting:

Time Sync Information:

Time Sync Period:

(X) Never

( ) Fixed at ______ seconds

( ) Configurable, range ______ to _______ seconds

a) Maximum time base drift over a 10 minute interval:             _________ ms
b) Maximum Internal Time Reference Error when set via DNP: _________ ms
c) Maximum Delay Measurement error: _________ ms
d) Maximum Response time: _________ ms
e) Event data time-tag error – if different than ( c ) :
f) Binary Input Change Events __________ ms
g) Counter Change Events __________ ms
h) Frozen Counter Change Events __________ ms
i) Analog Change Events __________ ms
j) Frozen Analog Change Events      __________ ms

Sends/Executes Digital Control Operations: 

SELECT/OPERATE**

DIRECT OPERATE**

DIRECT OPERATE – NO ACK**

 

Count > 1:

Pulse On:

Pulse Off:

Latch On:

Latch Off:

Trip/Close:

Raise/Lower:

 

Queue:

Clear Queue:

(X) Never

( ) Never

( ) Never

 

(X) Never

(X) Never

(X) Never

( ) Never

( ) Never

(X) Never

(X) Never

 

(X) Never

(X) Never


( ) Always

(X) Always

(X) Always

 

( ) Always

( ) Always

( ) Always

(X) Always

(X) Always

( ) Always

( ) Always

 

( ) Always

( ) Always


( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

 

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

 

( ) Sometimes*

( ) Sometimes*


( ) Configurable*

( ) Configurable*

( ) Configurable*

 

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

( ) Configurable*

 

( ) Configurable*

( ) Configurable*


*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must be selected.

Sends/Executes Digital Control Operations: 

SELECT/OPERATE**

DIRECT OPERATE**

DIRECT OPERATE – NO ACK**

 

Queue:

Clear Queue:


(X) Never

( ) Never

( ) Never

 

(X) Never

(X) Never


( ) Always

(X) Always

(X) Always

 

( ) Always

( ) Always


( ) Sometimes*

( ) Sometimes*

( ) Sometimes*

 

( ) Sometimes*

( ) Sometimes*


( ) Configurable*

( ) Configurable*

( ) Configurable*

 

( ) Configurable*

( ) Configurable*


*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

**To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.

The maximum number of objects supported in a single control request for objects 12 and 41.

Number of objects allowed for object 12: 1

Number of objects allowed for object 41: 1

Control Points per address:

(   ) Configurable

( X ) 1 control point per address

(   ) 2 control points per address

Do all indices support the same control codes:

( X ) YES – Controls codes 3 and 4

(   ) NO – attached points list stating configuration ability and supported control codes per point or group of points

Maximum Select/Execute Delay Time:

( X ) Not Applicable

(   ) Fixed at _____ seconds

(   ) Configurable, range ______ to ______ seconds

Ability for REMOTE/LOCAL control mode:

( X ) Not Applicable

(   ) Per point

(   ) Per object

(   ) Global

Sends Unsolicited Responses:

( X ) Never

(   ) Configurable (attach explanation)

(   ) Only certain objects

(   ) Sometimes (attach explanation)

Sends Static Data in Unsolicited Responses:

( X ) Never

(   ) When Device Restarts

(   ) When Status Flags Change

*No other options permitted.

ENABLE/DISABLE Unsolicited:

( X ) Not Supported

(   ) Configurable

(   ) Function codes 20,21 supported

Minimum number of events and/or minimum time before transmission of an unsolicited message.

Number of events: __________

Minimum amount of time (msec) : ___________


Assign Class Function code supported:

( X ) NO

(   ) YES

(   ) Per Object

(   ) Per Point

(   ) Configurable

Is the Event Buffer size configurable:

( X ) NO fixed size: _______

(   ) YES: range: __________ to __________

Configurable Per Class buffer:

( X ) NO

(   ) YES

Are the updated ENABLE/DISABLE unsolicited settings saved through a device reset:

(   ) YES

( X ) NO

Are the updated Assign Class settings saved through a device reset:

(   ) YES

( X ) NO

Supports Collision Avoidance:

( X ) Never

(   ) Always (attach explanation)

(   ) Configurable (attach explanation)

Source Address Filtering:

( X ) Not Supported

(   ) Configurable (attach explanation)

Supports Multi-drop communications:          (X) YES          (   ) NO 
Sends Multi-Fragment Responses:              (X) YES          (   ) NO 