Is it possible to apply redundancy to the SD+?

Created by Patrícia Siqueira, Modified on Mon, 8 Jan at 10:57 AM by Patrícia Siqueira

The SD+ can only be applied in physical redundancy using a ring architecture and a manageable switch. Due to the interconnection of Ethernet ports, it is not possible to apply redundancy to the SD+ through the PRP protocol since it cannot be connected to two separate networks without linking them (PRP requires both networks to be independent).

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article